Classification by Voltage Level
According to the voltage level, transformers are divided into 1000 kV, 750 kV, 500 kV, 330 kV, 220 kV, 110 kV, 66 kV, 35 kV, 20 kV, 10 kV, 6 kV, 0.66 kV, 0.38 kV, and 0.22 kV classes. Higher voltage classes serve transmission networks, while 6 kV to 35 kV classes serve distribution systems and below 1 kV serves end users.
Classification by Insulation and Cooling Medium
According to the insulation and heat dissipation medium, transformers are divided into dry-type and oil-immersed types. Dry-type transformers are further divided into cast-resin types with epoxy encapsulation and non-encapsulated types with class H insulation. Oil-immersed transformers use mineral or synthetic oil for insulation and cooling and suit outdoor and high-load installations.
Classification by Core Material
According to the core structure material, transformers are divided into silicon steel laminated transformers, silicon steel wound core transformers, and amorphous alloy core transformers. Amorphous alloy cores provide the lowest no-load loss for energy-saving designs.
Classification by Energy-Saving Series
According to the design energy-saving sequence, the series runs from older to newer: SG, SJ, S7, S9, S11, S13, and S15. Each generation reduces no-load and load losses, with S11 and above widely mandated in modern energy efficiency programs.
Classification by Phase and Capacity
By phase number, transformers are single-phase or three-phase. By capacity, the rated capacities follow the R10 priority series: 3, 5, 10, 15, 20, 25, 30, 40, 50, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000, and 5000 kVA.
Reading Transformer Model Designations
For the dry-type model SCB10-1000 kVA/10 kV/0.4 kV: S means three-phase (D means single-phase), C means resin cast windings, B means foil winding (R is wound winding, L is aluminum winding, Z is on-load voltage regulation, copper is unmarked), 10 is the design serial number, 1000 kVA is rated capacity, 10 kV is the primary voltage, and 0.4 kV is the secondary voltage. For the power transformer model SFSZ9-31500/110: S is three-phase, F is air cooled, S is three-winding, Z is on-load voltage regulation, 9 is the design number, 31500 is the capacity in kVA, and 110 is the primary voltage in kV. For SFPZ9-120000/110: three-phase, forced oil circulation air cooled, on-load voltage regulation, design number 9, capacity 120000 kVA, primary voltage 110 kV.
Box-Type Substations
Box-type transformers design traditional transformers in a box-type casing, with small size, light weight, low noise, low loss, and high reliability. They are widely used in residential areas, commercial centers, airports, factories, mines, hospitals, and schools. Box substations are generally divided by capacity in the national standard sequence: 315, 400, 500, 630, 800, 1000, 1250, 1600, and 2000 kVA.
Frequently Asked Questions
Q: How are transformers classified by cooling medium?
Into dry-type transformers with air or resin insulation and oil-immersed transformers using insulating oil for cooling and insulation.
Q: What does S in a transformer model mean?
S denotes a three-phase transformer; D denotes single-phase in the same position of the model designation.
Q: What does the number 10 mean in SCB10?
It is the design serial number, also called the technical serial number, indicating the design generation.
Q: What is the difference between the S9, S11, and S13 series?
They are successive energy-saving generations with progressively lower no-load and load losses.
Q: What does the capacity series follow?
Rated capacities follow the R10 priority coefficient series, such as 50, 80, 100, 125, 160, 200, 250 kVA and so on.
Q: What is a box-type substation?
A compact substation integrating transformer, switchgear, and controls in a box casing, widely used for distributed power supply.