Oil-Immersed Amorphous Alloy Transformer: SBH15-M Design and Loss Performance

Apr 07, 2024 Leave a message

An oil-immersed amorphous alloy transformer is a distribution transformer whose magnetic core is built from amorphous alloy ribbon instead of conventional grain-oriented silicon steel. The SBH15-M series described here is a sealed, full-oil-filled design: the core and windings are immersed in insulating oil inside a welded tank that is closed for life, so the oil does not come into contact with the outside air and the unit needs no separate oil conservator.

What Makes Amorphous Alloy Different

Amorphous alloy is a metallic glass. Its basic elements are iron, nickel, cobalt, boron and carbon, and the melt is quenched at about one million degrees per second so that the atoms freeze before they can arrange themselves into a crystal lattice. The result is a ribbon only 0.027 mm thick, roughly one tenth the thickness of a typical silicon-steel lamination.

Because there is no crystal structure, the material is an isotropic soft magnetic material: its magnetic properties are the same in every direction and magnetisation needs very little energy. Domain-wall motion meets no grain-boundary defects, so the power required to magnetise the core, and therefore the no-load loss, is far lower than in silicon steel. The same structure gives an electrical resistivity three to six times higher than that of silicon steel and a hardness about five times as high.

Core Material Properties

Property Amorphous alloy core Conventional silicon steel core
Ribbon thickness 0.027 mm 0.23-0.35 mm
Structure Amorphous, non-crystalline, isotropic Crystalline, grain-oriented
Electrical resistivity 3-6 times higher Reference level
Hardness About 5 times higher Reference level
Stress sensitivity High Moderate

Loss Performance of the SBH15-M Series

The SBH15-M30-1600/6-10 range covers ratings from 30 kVA to 1600 kVA with a high-voltage side of 6 kV to 10 kV. Within this range the load loss is about 15% below the values given in GB/T 6451, and the no-load loss is about 70% below the Group I values of the same standard. The implementation standard for the series is JB/T 10318-2002, which sets out the technical parameters of oil-immersed amorphous alloy core distribution transformers.

For a transformer the no-load loss is the part that is present twenty-four hours a day, whether or not the load is drawing power, so a 70% reduction has a larger effect on annual energy consumption than the same percentage reduction in load loss. That is why the amorphous alloy core is chosen first for transformers that stay energised around the clock with a low average loading, such as those in rural distribution networks and in industrial plants whose demand is intermittent.

Handling and Application Notes

Amorphous alloy is particularly sensitive to mechanical stress. Bending, clamping or support forces raise its no-load loss, so the core is carried in a structure that avoids concentrated pressure, and the wound core is stress-relieved after forming. Because the ribbon is very thin and hard, cutting and stacking follow dedicated tooling rather than the practice used for silicon steel laminations. The sealed tank also changes the maintenance routine: with the oil closed for life there is no oil sampling or topping-up, and the tank surface is designed to dissipate the heat of the core and windings without a conservator.

Where these controls are respected, the low no-load loss is preserved over the whole service life. The design suits distribution duty at 6 kV to 10 kV, and the loss advantage over a conventional silicon-steel unit grows the longer the transformer remains in service.

FAQ

Q: What is an oil-immersed amorphous alloy transformer?
A distribution transformer whose magnetic core is wound from amorphous alloy ribbon, sealed inside a full-oil-filled tank so that the oil never contacts the outside air.

Q: How much loss does the SBH15-M series save?
Load loss is about 15% below the GB/T 6451 values, and no-load loss is about 70% below the Group I values of the same standard.

Q: Why is amorphous ribbon so thin?
The melt is quenched at about one million degrees per second, which freezes the atoms before a crystal lattice can form, producing a ribbon only 0.027 mm thick.

Q: Why is amorphous alloy sensitive to stress?
It is a metallic glass with no crystal structure, so bending or clamping forces disturb its magnetic domain structure and raise the no-load loss.

Q: Which standard covers the SBH15-M series?
JB/T 10318-2002, the standard for the technical parameters of oil-immersed amorphous alloy core distribution transformers.

Q: Which ratings are available in the SBH15-M30-1600 range?
Ratings from 30 kVA to 1600 kVA, with a high-voltage side of 6 kV to 10 kV.