Types of special transformer oil leakage

Mar 05, 2024 Leave a message

1 air leakage

 

It is an invisible leak. Such as the leakage of air in and out of the casing head, the diaphragm of the oil conservator, the glass of the safety airway, and the weld blisters.

 

Moisture and oxygen in the air will slowly penetrate into the body through the leaked parts, and the seal between the inside and the outside of the transformer will be destroyed, causing problems such as moisture in the insulation and accelerated aging of the oil.

flyback transformer

2 oil leakage

 

2. 1 Internal leakage.

 

The oil in the bushing or the oil in the on-load tap changer chamber leaks into the transformer body.

 

2. 2 External leakage.

 

Weld leakage and seal leakage are the most common leakage phenomena.

 

Preventive measures for oil leakage in special transformers

500 kva transformer

1Choose seals with good material

 

When overhauling the transformer and dealing with leakage, seals with good high temperature resistance and oil resistance should be selected. The most commonly used sealing material in the domestic special transformer industry is nitrile rubber. Its oil resistance mainly depends on the acrylonitrile content in the nitrile rubber. The higher the acrylonitrile content, the better the oil resistance, the greater the hardness, and the less likely it is to deform.

 

In general, nitrile rubber with a Shore hardness between 70 and 80 should be selected. When identifying the oil resistance of the gasket, the aging test of the gasket and the compatibility test with special transformer oil should generally be done. The gasket should be immersed in hot oil at 120°C for 168 hours, and then the change rate of its weight, volume and hardness should be measured. Select It has little deformation and meets standard seals.

 

2Choose high-quality butterfly valves

 

As the butterfly valve, choose ZF80 vacuum eccentric butterfly valve. Compared with ordinary butterfly valves, the mechanical strength and surface finish of the vacuum eccentric butterfly valve have been greatly improved, and the biggest advantage of this product is that it adopts double-layer sealing at the interface with the transformer flange, which eliminates Oil leakage problem at transformer interface.

 

3 Use electric welding to plug leaks

 

Electric welding can be used to plug the pores and blisters left by casting of special transformers, as well as the welding seams and solder joints that have weak welding, desoldering, and cracks.

 

The leakage point should be identified before plugging welding. If the leakage point is smaller, the leakage point can be killed directly with electric welding. If the leakage point is larger, asbestos rope or metal filler should be filled first, and then surfacing around it, and then a small welding rod should be used. Rapid arc ignition and repair welding with high current.

 

4 Standard seal replacement process

 

For special transformers of different models and capacities, whether flange connection or threaded connection is used, the dust and rust on the connection surface must be removed before replacing the seal. After cleaning the seal, apply sealant on both sides of the seal. Glue (usually 609 polymer liquid sealant is used). After the sealant dries for a period of time and the solvent evaporates, tighten the flange and screw connections.

 

5. Improve the level of installation technology and eliminate leakage caused by improper installation methods.

 

If the flange interface is uneven or deformed and misaligned, correct the interface first. If the misalignment is serious and cannot be corrected, the flange can be cut off and re-welded. Make sure the interfaces are parallel. During installation, the compression amount of the gasket is approximately 1/3 of its thickness.

 

6 Quick sealing and plugging glue stick

 

This method is used for small leaks and drips in transformers. This method can be used to plug leaks in special transformers where the radiator tube wall is thin and where the leakage points are not suitable for welding plugging.

When using a plugging glue stick to plug a leak, the oil, paint, and oxides in the plugged area must be completely removed so that the metal can reveal its true color. Then adjust the sealing glue according to the proportion and seal the leakage area until there is no leakage.

 

Summarize

 

With the development of the transformer industry, how to improve the performance of special transformer equipment and ensure the reliable operation of special transformers is an urgent problem that needs to be solved in transformer production. Therefore, whether the problem of oil leakage in special transformers can be dealt with promptly and thoroughly is also It has gradually become an important technical indicator to measure the development of the transformer industry.