How to choose the thickness of DX52D ductwork?
A: Rectangular ductwork: 0.5mm for long side ≤ 630mm, 0.6mm for 630–1250mm, and 0.75mm for 1250–2000mm; Circular ductwork conforms to GB 50243, with a galvanized layer ≥ Z80.
Can DX52D be used in load-bearing structures?
A: It cannot be used for main load-bearing structures (beams, columns, supports); it can only be used for non-load-bearing/secondary structures (purlins, joists, enclosure frames), and must be verified according to the light steel structure code.
What are the requirements for using DX52D in coastal buildings?
A: A Z275 high-zinc coating or zinc-aluminum-magnesium (ZM) coating must be used; it is recommended to use color coating (PVDF), and seal the joints with sealant to avoid chloride ion corrosion.
What is the relationship between DX52D and color-coated steel sheet (PPGI)? A: DX52D is a color-coated substrate; DX52D+Z+PE/PVDF is commonly used in construction, combining molding, corrosion resistance, and decorative properties, with a lifespan 5-10 years longer than bare galvanized steel.
Precautions for using DX52D in gutters/rainpipes?
A: Thickness ≥ 0.7mm, galvanized layer ≥ Z180; joints should be welded + sealed with adhesive to avoid water accumulation and corrosion; regularly clean debris to prevent localized corrosion and perforation.