S11-35KV oil-immersed electrical transformer

Apr 07, 2024 Leave a message

Product Applications

Power plant, power system, coal and mine, transportation,etc.

Technical Parameter

Type Rated power KVA Rated voltage (KV) Connection sections Loss(KW) No-load current (%) Short-circuit impedance (%)
HV LV No-load load (75℃)
S11-50/35 50 35±15% ±2x25% 0.4 Yyno 200 1210 1.8 6.5
S11-100/35 100 300 2020 1.62
S11-125/35 125 340 2380 1.56
S11-160/35 160 360 2835 1.48
S11-200/35 200 430 3300 1.39
S11-250/35 250 510 3960 1.26
S11-315/35 315 610 4760 1.26
S11-400/35 400 733 5760 1.16
S11-500/35 500 860 6900 1.16
S11-630/35 630 1040 8280 1.1
Model rated capacity (KVA) rated voltage(KV) connection group 损耗(KW) Short-circuit impedance (%) No-load current (%)
high voltage (HV) Low voltage (LV) No-load loss(W) Load loss(45℃)
S11-800/35 800 35±15% ±2x25% 38.5±5% 35×5% 10.5 6.3 3.15 Yd11 1.23 9.9 0.9 6.5
S11-1000/35 1000 1.44 12.1 0.9 6.5
S11-1250/35 1250 1.76 14.6 0.81 6.5
S11-1600/35 1600 2.12 17.5 0.76 6.5
S11-2000/35 2000 2.16 17.8 0.67 6.5
S11-2500/35 2500 3.15 20.7 0.67 8.5
S11-3150/35 3150 38 24.3 0.63 7.0
S11-4000/35 4000 4.25 28.8 0.63 7.0
S11-5000/35 5000 5.4 33 0.54 7.0

Features

1)Low loss

The iron core is made of high-quality Hi-B cold-rolled silicon steel sheets, which are cut longitudinally and horizontally using a fully automatic lamination machine. The multi-level fully inclined seam is fully automatic lamination, and the iron core binding adopts the overall pressurization and PET tape binding process, effectively reducing the no-load loss and current of the transformer.

 

2)Low noise

The noise of oil immersed self cooling transformers is mainly caused by electromagnetic noise from the iron core. In order to reduce the noise, our company has taken the following measures:

Low magnetic flux density design;

High quality high magnetic silicon steel sheet;

Adopting a Swiss fully automatic laminating machine to control the stacking accuracy;

Reliable clamping and support measures;

Special shock absorption measures.

 

3) No leakage

The oil tank and storage tank have undergone positive and negative pressure leak testing to ensure that there will be no oil leakage during normal operation of the product. The component installation adopts a flange groove structure, which is formed in one go. All sealing components are made of high-quality one-time formed acrylic rubber parts to prevent oil leakage.

 

4)Strong short-circuit resistance

In order to ensure that the transformer can withstand the impact of short-circuit current and apply rated voltage on the primary side, under the condition of complete short-circuit on the secondary side, without causing thermal and mechanical damage under the action of short-circuit current, our company has taken the following measures during design and manufacturing:

Reasonably calculate the ampere turn balance of the transformer coil using semi hard copper wire;

The strength and stiffness of the iron core clamping components are calculated to meet the safety requirements of maximum short-circuit mechanical force;

The winding pads are uniformly densified and made of high-density hard cardboard;

The winding adopts a reasonable structure with evenly distributed and compressed compression blocks, with uniform assembly height and uniform stress, ensuring the ability to withstand short circuits;

Take some special measures to prevent the deformation of the coil under force.

Oil immersed current transformer
Oil immersed self cooled transformer
Oil immersed distribution transformer
Oil immersed type transformer
Oil immersed power transformer
Three phase oil immersed transformer