SCBH15-10KV Amorphous alloy transformer

Apr 07, 2024 Leave a message

Products applications

Semiconductor factory, LCD factory, High-rise building, subway, express railway, thermal power plant, transformer station, petrochemical plant, hospital, athletic stadium, performance place, car factory, rolling factory, airport, port, hydro-poewr plant, water treatment facility, power utility, EV charging, renewable energy, etc.

Technical Parameter
Power(kVA) Load loss (W) No-load current (%) Load loss (W) Impedance (%)
Secondary energy efficiency Primary energy efficiency
B(100℃) F(120℃) H(145℃) B(100℃) F(120℃) H(145℃)
30 70 1.6 670 710 760 635 675 720 4.0
50 90 1.4 940 1000 1070 895 950 1015 4.0
63 120 1.3 1290 1380 1430 1225 1310 1405 4.0
80 130 1.2 1480 1570 1690 1405 1490 1605 4.0
100 150 1.1 1740 1850 1930 1655 1760 1880 4.0
125 170 1.1 2000 2130 2280 1900 2025 2165 4.0
160 200 1.0 2370 2530 2710 2250 2405 2575 4.0
200 230 1.0 2590 2760 2960 2460 2620 2810 4.0
250 280 0.9 3270 3470 3730 3105 3295 3545 4.0
315 310 0.8 3750 3990 4280 3560 3790 4065 4.0
400 360 0.8 4590 4880 5230 4360 4635 4970 4.0
500 420 0.7 5530 5880 6290 5255 5585 5975 4.0
630 410 0.7 5610 5960 6400 5330 5660 6055 6.0
800 480 0.7 6550 6960 78460 6220 6610 7085 6.0
1000 550 0.6 7650 8130 8760 7265 7725 8320 6.0
1250 650 0.6 9100 9690 10370 8645 9205 9850 6.0
1600 760 0.6 11050 11730 12580 10495 11145 11950 6.0
2000 1000 0.5 13600 14450 15560 12920 13725 14780 6.0
2500 1200 0.5 16150 17170 18450 15340 16310 17525 6.0
amorphous alloy transformer features

The iron core is wound by non-crystalline alloy strips, and a three-phase five-column or three-phase three-column winding iron core structure is adopted according to the requirements. The iron core cross section is rectangular;the high voltage coil adopts segmented cylindrical coil, which is vacuum-casted with thin insulation sealing.

The large capacity winding has axial air duct, high power frequency withstand voltage, low local discharge, dust prevention and good cooling effect; the low voltage coil adopts laminating coil, which is pre-immersed and hot-cured between layers, which effectively solves the insulation imbalance problem when low voltage and large current coils are wound by wires.

At the same time, there is no axial winding angle in the laminating coil, and the axial force that the transformer bears when short-circuiting is greatly reduced.

The process is good, the additional loss is low, and the anti-short-circuit ability is strong; according to the user's needs, common steel plate, aluminum alloy or stainless steel shell can be configured, and the protection level can be selected from IP20 and IP23, and the high and low voltage busbar inlet and outlet interfaces can be configured according to the user's needs.

Amorphous steel core transformer
Amorphous core transformer
Amorphous steel transformer
Amorphous transformer
Amorphous steel core
Amorphous core